Monitor
The sensing network continuously compares the incoming phases of the three-phase voltage.
Phase-Guard continuously monitors phase-voltage balance and works with magnetic controls to stop motors and other equipment from operating under damaging phase conditions.

Phase-Guard is a self-contained power-sensing device—not a thermal device. It responds directly to abnormal conditions in the three-phase supply.
The sensing network continuously compares the incoming phases of the three-phase voltage.
When a phase becomes more than 12% unbalanced or phase loss occurs, the unit recognizes the fault.
The master output relay trips after an approximately 1½-second delay, helping prevent nuisance trips.
Protection thresholds and timing can be tailored using the Phase-Guard Admin Software.
Select the standard operating behavior for your control circuit. Add the Normal Relay Selector option to switch modes later through software.
The output relay is energized while monitored power conditions are normal.
View Model P details →The output relay remains de-energized while monitored power conditions are normal.
View Model PND details →Use Admin Software to adjust device settings and match your specific operating environment.
Explore Admin Software →License additional capabilities after installation, without replacing or shipping the device back.
See the upgrade process →Keep units ready in inventory, then configure or upgrade them for the application before deployment.
Browse available options →Phase-Guard monitors a three-phase supply line and works with controls including push-button stations, thermostats, pressure switches, and float switches. It can also support manually operated starters with shunt or capacitive trip devices.
Standard models are available for 120, 208, 240, 480, 550, and 600 VAC operation.
Protect motors of any horsepower rating at the selected operating voltage.
Protect one motor or multiple motors fed from a common contactor or magnetically latched circuit breaker.
After a phase fault clears and normal conditions return, Phase-Guard automatically resets unless configured otherwise.
Connect three-phase power at L1, L2, and L3. DPDT master-relay contacts rated 30 amps at 277 VAC can open or close the customer’s protection circuit.